Site visit made on 19 August 2025
by O Marigold BSc DipTP MRTPI
an Inspector appointed by the Secretary of State
Decision date: 28 August 2025.
Appeal Ref: 6000297
74 Treen Avenue, Barnes, Richmond Upon Thames, London SW130JT
• The appeal is made under section 78 of the Town and Country Planning Act 1990 (as amended)
against a refusal to grant planning permission.
• The appeal is made by Michael Olstowski against the decision of the Council of the London Borough
of Richmond Upon Thames.
• The application Ref is 24/2002/HOT.
• The development proposed is described as “retrospective application: installation of an air heat pump
to the rear of the property”.
Decision
1. The appeal is dismissed.
Preliminary Matters
2. I have taken the description of development above from the Council's Decision
Notice, which is more concise than that used in the application form. However,
although described as retrospective, I saw that the installed position of the pump is
alongside a rear window, whereas the submitted elevations show it being below
the window’s cil level. I shall therefore base my decision on the plan before me, as
a proposal, rather than for the pump as installed on site. I am satisfied that no
party would be prejudiced as a result.
Main Issues
3. The main issues are the effect of the proposal on:
• the character and appearance of the area, and
• the living conditions of occupiers of nearby dwellings, in respect of noise.
Reasons
Character and Appearance
4. The site consists of a two-storey dwelling in a row of similar terraced properties,
with relatively short rear gardens. The pump would be located on the rear
elevation of the dwelling. As such, there would be few if any publicly obtainable
views of it, and only limited views from the windows of the adjoining dwellings.
5. Nevertheless, the pump would be a structure of functional design and would sit
proud of the rear elevation of the house, in a raised position, albeit behind the
projection of one of the adjoining dwellings. Accordingly, it cannot be said to
respect the form of the property or the row, and instead the pump would appear
utilitarian and industrial in appearance. Consequently, it would appear out of place.
Appeal Decision 6000297
2
6. I understand that the appellant intends to relocate the pump to a lower level, when
construction of a rear extension has been completed. I saw that the unit installed
on site has the cabling to enable this. That said, the proposal as shown on the
plans is for a pump at first floor level. I must therefore determine the appeal on this
basis.
7. For the reasons given above, the proposal would harm the character and
appearance of the area, contrary to policy LP1 of the Council’s Local Plan,
adopted July 2018. This requires that development must respect and contribute
towards local environment and character, including its form. For the same reasons,
it would conflict with the similar requirements of policy 28 of the publication draft of
the emerging Local Plan.
Noise
8. The appellant has provided a desktop noise assessment using the criteria set out
in the Council’s Supplementary Planning Document (SPD)1. This desktop
assessment identifies the distance between the as-installed pump and the closest
neighbouring windows, and states that use of the pump would be infrequent and at
daytime. Even so, it would be difficult if not impossible to prevent a more frequent
or nighttime use of the pump.
9. The desktop assessment provides the noise specifications of the pump, the
manufacturer’s maximum noise levels, and predicted noise levels based on site
circumstances. These include that the adjacent neighbouring windows are on walls
set behind or forward of the wall hosting the pump. The resultant noise levels are
said to be below the minimum amount indicated in the SPD.
10. However, the manufacturer’s noise measurements are taken from within an
anechoic chamber and so may be higher in actual installation conditions. As such,
the Council’s unchallenged technical evidence is that the sound power level needs
to be calculated and then converted to the sound pressure level. On this basis,
and taking into account the distance involved, the pump would exceed the
nighttime limit required by the SPD, by an appreciable amount.
11. The short length of the gardens of the dwellings nearby means that they may well
be intensively used relatively close to the proposed pump, adding to its potential
adverse effects. The appeal site is subject to background noise from road use,
frequent trains close by, and aviation flight paths overhead. However, the detailed
evidence of the Council, albeit using aggregated values, shows that the appeal site
is not particularly affected by transport-related noise. It follows that this does not
provide a reason to justify a deviation from the SPD standard.
12. Positioning the pump at a lower level would provide noise barriers in the form of
boundary fencing, as might an acoustic enclosure, but these do not form part of
the proposal being considered. The absence of objections from the occupiers of
the adjoining dwellings does not necessarily indicate that the pump would have an
acceptable effect on their living conditions. The appellant says that the Council’s
officer was unable to detect sound emissions from the installed pump, but I have
no substantive evidence of actual recorded noise levels from it.
1 Development Control for Noise Generating and Noise Sensitive Development adopted September 2018.
Appeal Decision 6000297
3
13. For these reasons, a more detailed, bespoke acoustic assessment is required, for
example over a whole nighttime period, and over several days to identify any
diurnal patterns. In its absence, I cannot conclude that the proposal would have an
acceptable effect on the living conditions of occupiers of nearby dwellings in
respect of noise. Accordingly, it would conflict with Local Plan policies LP8 and
LP10, which seek to protect living conditions and avoid detrimental effects to
health, including from noise. It would also conflict with similar policies LP46 and
LP53 of the publication draft of the emerging Local Plan.
Other Matters
14. The pump would allow for environmentally friendly heating, but this relatively small
benefit to a single dwelling does not overcome my concerns. On my visit, I saw
other units installed in more prominent locations on nearby dwellings and
commercial properties. Nevertheless, I do not have full details of these
installations, their planning or enforcement background, or the level of noise that
they generate. As such, I can make little useful comparison between these
examples and the proposal before me.
15. The pump is said to be permitted development, in accordance with Schedule 2,
Part 14, Class G of the General Permitted Development Order 2015 (GPDO) in
relation to air source heat pumps. However, the legislation makes requirements
beyond those referred to by the appellant. On the information before me, I cannot
be certain that the GPDO criteria would all be met, and therefore that it would be
lawful. The application is for planning permission, rather than a Certificate of
Lawful Development, and so I have determined the appeal solely on its planning
merits.
16. The appellant has expressed concerns about the handling of the planning
application by the Council, inconsistent advice given, and the length of time that
the Council has taken to make its decision. Whilst this must have caused distress,
it does not materially change my consideration of the planning merits of the appeal
proposal.
Conclusion
17. For the reasons given, I have found conflict with the Development Plan as a whole.
The material considerations in this case do not indicate a decision other than in
accordance with the Development Plan. This leads me to conclude that the appeal
should be dismissed.
O Marigold